Page 82
The
fourth parameter
and the
fifth parameter
for each relay set the
pump
“
ON
” and “
OFF
” points, which are entered in
Measurement units P104
.
For
pump down
the “
ON
” is set
higher than
“
OFF
”. For
pump up
then
“
ON
” is set
lower than
“
OFF
”. See the appropriate
pump duty,
function
table (
P212, 222, 232, 242, 252
) for further information.
P213, P223, P233, P243, P253 - Relay Setpoint 1
This parameter determines the “
ON
” point of the pump.
P214, P224, P234, P244, P254 - Relay Setpoint 2
This parameter determines the “
OFF
” point for the pump.
The
sixth parameter
will determine the
service ratio
that will be used to
switch the pump, when
pump duty
selected is a
Service Ratio
duty.
P211, 221, 231, 241, 251 = 6, 7 or 9 (Service ratio)
P215, P225, P235, P245, P255 - Relay Setpoint 3
This parameter determines the Service Ratio in values of %. See the
appropriate
pump duty
function, table (
P211, 221, 231, 241, 251
), for
further information.
P219, P229, P239, P249, P259 - Relay Max.Rate
This parameter will allow a
pump
to be
switched
at a pre-determined
Rate
of change of Level
, irrespective of the “ON” level setpoint P213, 223, 233,
243, 253. Once a pump relay has been switched “
ON
” by the pre-
determined
Rate of Change
, it will remain energised until the level reaches
the “
OFF
” level setpoint
P214, 224, 234, 244, 254
.
Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level)
values.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...