Example 2 BS3680 U-Throated Flume
In this example it is required to calculate to BS3680 the flow through a U-
Throated Flume without any hump. Absolute calculation will be used, and
there is a requirement for an alarm to indicate a low flow condition which
will be set to Relay 1. The flow rate is to be displayed in
millions
of
US
gallons/hour
and the totaliser is also to record the flow in
millions
of U
S
gallons
, the resettable totaliser is to be displayed during RUN. The
transducer to be used is a dB3.
The distance from the face of the transducer to
zero
flow (
P105
) is 35
inches and
max head
(
P704
) is 15 inches,
maximum flow
(
P705
) which
will be calculated by the
FlowCERT
LITE
as 0.1784 Mil USG/Hour
The dimensions of the flume are as follows:
Approach
Channel
diameter
(
Dim “A”
)
P710
= 28 inches
Throat diameter
(
Dim “B”
)
P711
= 20 inches
Throat length
(
Dim “C”
)
P712
= 40 inches