Page
105
Bargraph
P829 Bargraph
By default the bargraph will be representative of the reading obtained, as
determined by the
Mode P100
. This parameter is automatically set to the
correct default option when selecting the
Mode P100
and
Xducer
(
P101
),
and under normal circumstances will not require changing.
The options, dependant on the
value
entered for
Mode P100
, are as follows:
Option
Description
1 = Level
Bargraph
will be r
epresentative
of
level
.
2 = Head (Default)
Bargraph
will be
representative
of
head
.
3 = Flow
Bargraph
will be
representative
of
flow
.
mA Output Parameters
Range
P830 mA Range
This parameter determines the range of the mA output, from the following.
Option
Description
0= Off
mA output disabled.
1= 0 to 20 mA
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 0 mA. If
the reading is 100% the output is 20 mA.
2= 4 to 20 mA
(Default)
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 4 mA. If
the reading is 100% the output is 20 mA.
3= 20 to 0 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 0 mA.
4= 20 to 4 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 4 mA.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...