Page 112
Filters
The following two parameters can be used to filter out unwanted changes of
level caused by a ‘rippled’ or agitated surface.
P880 Gate Mode
This parameter determines the operation of the gate that is established
around the echo being processed and is used to track the echoes movement
and update the level measurement indication on the display. Please consult
Pulsar for further information and assistance on changing the value of this
parameter,
Default = 0 (Fixed)
P881Fixed Distance
This parameter determines the width of gate to be used in tracking an echo
and under normal circumstances will not require changing, but it can be
increased in the cases where the surface is moving extremely fast (in excess
of 10m/min) to ensure smooth processing of the changing level.
P882 Process Filter
This parameter determines the number of ‘cycles’ that will be taken before a
change in level is processed and the display updated.
Option
Description
1 = Fast
level will be updated every cycle
2 = Medium
level will be updated every 8 cycles
3 = Slow (Default)
level will be updated every 16 cycles
P884 Peak Percentage
When P102 = 2 (Solids), this parameter can be used to determine the point
at which the measurement is taken, within the established gate of the
selected echo, in order to compensate for any error that maybe caused by
“angles of repose” presented by the way the material settles. Please consult
Pulsar, for further information and assistance on changing the value of this
parameter.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...