Page 114
P906 Side Clearance
This parameter is used to set the distance by which the DATEM trace will
“stand off” from around unwanted echoes such as obstructions. Please
consult Pulsar for further information and assistance on changing the value
of this parameter.
System Parameters
Passcode
P921 Enable Code
Enables
the passcode (
P922
), which means the passcode must be entered to
go into program mode. If
disabled
(set to
0
), then no passcode is required,
and
ENTER
is used to enter program mode.
Default =1 (Enabled)
P922 Passcode
This is the passcode that must be used to enter program mode. The
default
is
1997
, but this can be changed to another value from 0 to 9999.
Backup
P925 Parameter Backup & Restore
This parameter is used to make a backup of all parameters, for example to
ensure a default set is maintained within the unit. If alterations are made to
the parameters that do not work as intended, then the backup set can be
restored into the unit.
You can make two separate backup copies if you wish, called backup 1 and
backup 2, and restore from either.
The options are:
Option
Description
1= Backup 1
Make backup to area 1 of all parameters
2= Backup 2
Make backup to area 2 of all parameters
3= Restore 1
Restore all parameters from area 1
4= Restore 2
Restore all parameters from area 2
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...