Example 3 BS3680 Rectangular Weir
In this example it is required to calculate to the flow through a BS3680
Rectangular weir. Absolute calculation will be used, and there is a
requirement for an alarm to indicate a high flow condition to be set to Relay
3. The flow rate is required to be displayed in
US gallons/minute
and the
totaliser is to record the flow in
thousands
of
US gallons
, the resettable
totaliser is to be displayed during RUN. The transducer to be used is a dB3.
The distance from the face of the transducer to
zero
flow (
P105
) is 40
inches and
max head
(
P704
) is 16 inches,
maximum flow
(
P705
) will be
calculated by the FlowCERT
LITE
as 2385.63 USG/min.
Approach
width
(
Dim”A”
)
P710
= 18 inches
Crest width
(
Dim “B”
)
P711
= 12 inches
Crest Height
(
Dim “C”
)
P712 =
10 inches