P146 Tel. No2
This parameter is used to enter to enter the next 6 digits, following the ‘0’s,
of the telephone number to be dialled. If there are less then 8 digits
following the ‘0’s then just enter the digits required, if there are more than
digits following the ‘0’s then enter the first 6 digits and then proceed to
P147 and enter the remaining digits.
P147 Tel. No3
This parameter is used to enter any remaining digits of the telephone number
to be dialled after completion of P145 and P146 above.
Example
Telephone number to be dialled is: 0 1234 123456
P145 Tel. No. 1 = 1(One ‘0’ at the beginning of the telephone number)
P146 Tel. No. 2 = 123412 (The next 6 digits following the ‘0’s).
P147 Tel. No. 3 = 3456 (Remaining digits of telephone number).
P148 Timed Out
This parameter will set the time period that the unit will wait for a reply
before disconnecting.
Default = 90 seconds
P149 Retry No.
This parameter will set the number of times the telephone number will be re-
dialled if no reply is received. If set to ‘0’ then the number will be re-dialled
continually until a reply is received, if set to ‘-1’ then number will not be re-
dialled at all. Any other value entered between 1 and 99 will determine the
number of re-dials to be attempted.
Default = 0
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...