Page 72
P106 Span
This parameter should be set to the maximum distance from the
Empty
Level
(
P105
) to the maximum material level. It is automatically set to be
equal to the
Empty
Level
(
P105
) less the
Near
Blanking
distance (
P107
),
when you set the empty level.
P107 Near Blanking Distance
This parameter is the distance from the face of the transducer that is not
measurable, and is pre-set to the minimum value dependant on the Xducer
(P101) selected. It should not be set to less than this figure, but can be
increased, typically to ignore close in obstructions.
Transducer
Near Blanking Distance
P101 = dBMach3 Transducer Default Blanking Distance = 0.00 inches
P101 = dB3 Transducer
Default Blanking Distance = 4.921 inches
P101 = dB6 Transducer
Default Blanking Distance = 11.811 inches
P101 = dB10 Transducer
Default Blanking Distance = 11.811 inches
P101 = dB15 Transducer
Default Blanking Distance = 19.685 inches
P101 = dBS6 Transducer
Default Blanking Distance = 7.874 inches
P108 Far Blanking Distance
This is the distance (as a
percentage
of
empty level P105
) beyond the
empty point that the unit will be able to measure, and by
default
is pre-set to
10%
of the empty level.
If the surface being monitored can extend beyond the
Empty
Level
(
P105
)
then the far blanking distance can be increased to a maximum of 100% of
empty level.
This parameter is always entered as a % of empty level.
Important Information
When using the
dB 3
the
maximum
distance,
that can be measured
inclusive of far end blanking
is
118.116 inches
.
Summary of Contents for FlowCERT LITE
Page 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Page 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Page 37: ...Page 29 This page left blank intentionally...
Page 77: ...Page 69...
Page 135: ...Page 127 This page left blank intentionally...