Communications Using the Controller I/O Cable
ZX-GT User’s Manual
92
Assignment of input signal wires
Cable color Signal
Function
Pink
Bank switching input
Bank 1 is selected when this input is OFF, and bank 2 is
selected when this input is ON.
Bank switching is enabled only when the bank switching
source is set to "I-O".
Switching Banks p.85
Orange
Zero reset input
Sets the measured value to zero.
• At zero reset execution
Turn the zero reset signal ON for 0.2 to 0.8 seconds.
After the zero reset signal turns OFF, the zero reset is
executed within one measurement cycle.
• At zero reset cancellation
Turn the zero reset signal ON for at least
1 second. The zero reset is cancelled within one
measurement cycle after 1 second elapses.
Purple
Timing input
Use this input for hold function timing.
The sub-display will show "TIMIG" while the hold function
timing is input.
Red
Reset input
This input resets all outputs.
When this input is ON, internal calculations are
discontinued, all judgment outputs are turned OFF, and
the maximum value (approx. 5.5 V at voltage output or 23
mA at current output) is output as the analog output.
The sub-display will show "RESET" while the reset is
input.
zx_gt.book Page 92 Wednesday, May 30, 2007 3:29 PM
Summary of Contents for ZX-GT -
Page 1: ...Smart Sensor Cat No Z263 E1 01 ZX GT Series USER S MANUAL...
Page 12: ...ZX GT User s Manual 10 MEMO...
Page 17: ...CONTENTS ZX GT User s Manual 15 MEMO...
Page 20: ...Operation Step Guide ZX GT User s Manual 18 MEMO...
Page 42: ...Initializing Controller Settings ZX GT User s Manual 40 MEMO...
Page 50: ...Functions and Operations during Operation RUN Mode 48 ZX GT User s Manual MEMO...
Page 90: ...Special Functions ZX GT User s Manual 88 MEMO...
Page 157: ...Compliance with EC Directives ZX GT User s Manual 5 APPENDICES 155 MEMO...
Page 162: ...Quick Reference for Displays ZX GT User s Manual 160 MEMO...