![background image](http://html1.mh-extra.com/html/omron/smartslice-grt1-drt/smartslice-grt1-drt_operation-manual_742293173.webp)
153
Analog Output Units
Section 5-5
6. To set the monitor value, click the
Cumulated Count
Tab, and input the
desired value in the
Threshold Cumulated Counter
Field.
7. Return to the
General
Tab Page, click the
Download
Button, and then
click the
Reset
Button to reset the Unit.
8. Click the
OK
Button to exit.
Setting Output Value
for Errors
The Output Unit value that is output when communications errors (timeout
and BusOff errors) or slice bus errors occur can be set in word units. The four
output value settings are set using the Setting Tool.
Setting Patterns
Output Ranges and
Values
Note
When a node address has been used more than once or a Unit error has
occurred, the current output will be 0 mA and the voltage output will be 0 V,
regardless of the setting.
Low limit
Outputs the values in the following table according to the output range.
High limit
Outputs the values in the following table according to the output range.
Hold last state
Holds and outputs the value from immediately before the error occurred.
Zero count
Outputs the value when 0 is written from the Host. This setting will be affected by scaling
settings that are used.
Output range
Low limit
High limit
Hold last state
0 to 5 V
–0.25 V
5.25 V
Holds value.
1 to 5 V
0.8 V
5.2 V
Holds value.
0 to 10 V
–0.5 V
10.5 V
Holds value.
–10 to 10 V
–11 V
11 V
Holds value.
4 to 20 mA
3.2 mA
20.8 mA
Holds value.
0 to 20 mA
0 mA
21 mA
Holds value.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......