198
Temperature Input Units
Section 6-4
3. Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where top/valley counter is to be set, and
select the
Top/Valley
Option
in the
Function Choice
Area.
5. Select the
Top/Valley
Tab and select either
Top Count
or
Valley Count
from the pull-down menu on the
Count Type
Field.
6. A threshold count value can be set in the
Threshold Top/Valley Counter
Field.
7. Return to the
General
Tab, click the
Download
Button, and then click the
Reset
Button to reset the Unit.
8. Click the
OK
Button and exit the window.
Rate of Change
Calculation
The rate of change can be obtained for each sampling cycle set for the tem-
perature input data. This function calculates the difference between each set
sampling cycle and value obtained in the previous cycle. The sampling cycle
can be set between 250 ms and 65,500 ms in 250-ms increments. The default
setting for the sampling cycle is 250 ms.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......