149
Analog Output Units
Section 5-5
4. Select the tab page for the output to be adjusted, and click the
Adjustment
Button. (At the same time, set the output range again.)
Adjusting the Low Limit
5. Output the value that is equivalent to 0% from the Master Unit. Always per-
form adjustment with the 0% value.
6. Adjust the analog value that is output from the terminal using the Low Limit
slide bar, as shown in the following window. Repeat adjustments until the
correct 0% value is output from the output device. After compensation is
completed, click the
Fix lower adjusting Value
Button.
7. To return to the default settings, click the
Default Setting
Button
8. Close the Adjustment Window, return to the
General
Tab Page, click the
Download
Button, and then click the
Reset
Button to reset the Unit.
9. Click the
OK
Button to exit.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......