219
Temperature Input Units
Section 6-4
Note
The terminal block temperature stabilization time does not affect the
upper/lower limit adjustment, so the adjustment can be performed immedi-
ately if 30 minutes have passed since the Temperature Input Terminal’s
power was turned ON.
Step
Timing chart
Stabilization time
Input Unit’s power supply ON
Wiring for input 1 upper/lower limit
adjustment
Input 1 upper/lower limit adjustment
Change wiring for input 1 bias
compensation
Input 1 bias compensation
Change wiring for input 2
upper/lower limit adjustment
Change wiring for input 2 bias
compensation
Input 2 bias compensation
(End of adjustment)
Wait at least 30 minutes.
(Check whether additional
time is required for devices
such as the STV, DMM,
and ZERO-CON.)
60 minutes min.
60 minutes min.
Temperature
Input Terminal’s
stabilization time
Terminal Block temperature
stabilization time 1 after wiring
is changed.
Terminal Block temperature
stabilization time 2 after wiring
is changed
Input 2 upper/lower limit adjustment
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......