95
Status Areas
Section 5-2
Output Data
GRT1-DA2
@
Analog
Output Units
Analog Output Units support one type output data. Allocate the required data
as shown in the following tables.
Output Data
5-2
Status Areas
An Analog I/O Unit has two internal Status Areas. Bits are set with respect to
thresholds set by the user for each function. When any bit turns ON in one of
these Status Areas, the relevant Communications Unit Status Flag turns ON.
The Master Unit is notified of the status of Communications Unit Status Flags.
Information in I/O Unit Status Areas can be read using the Setting Tool.
GRT1-AD2
Warning Status Area
The Analog Input Unit’s Warning Status Area is configured of the following 16
bits. The Warning Status Area provides notification of minor errors detected in
the Unit.
I/O data
Details
Hold Flags (1 output byte)
Used with each of the hold functions (peak, bottom, top, and valley) to control the execu-
tion timing of hold functions from the Master.
Data Type
Details
Output data (4 output bytes)
Used to allocate analog output data.
Host Master
Comm
u
nications Unit
Analog I/O Unit
When any Analog I/O Unit Stat
u
s Flag
t
u
rns ON, the relevant Comm
u
nications
Unit Stat
u
s Flag t
u
rns ON.
The threshold is exceeded
and the relevant
b
it t
u
rns ON.
The Setting Tool can
b
e
u
sed
to read
w
hich
b
its are ON.
Notification to
Master
Bit
Contents
Description
0
Reserved.
---
1
Reserved.
---
2
Reserved.
---
3
Unit Maintenance Flag
OFF: Normal; ON: Error
(Over threshold or 87672
hours)
Monitors the power-ON time set as the
threshold for the Unit conduction time
monitoring function.
Also monitors whether 87672 hours (10
years) have elapsed.
4
Reserved.
---
5
Reserved.
---
6
Reserved.
---
7
Reserved.
---
8
Analog Range Flag
OFF: Within range (below
monitoring set value)
ON: Out of range (at or
above monitoring set
value)
Turns ON when the analog data
exceeds the range that can be dis-
played or the monitoring value set for
the monitor function.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......