312
Explicit Messages
Appendix A
Number of
AD Conver-
sion Points
Setting
Write/
Read
Sets the number of AD
conversion points.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
64 hex
2 bytes
1 byte
Input
Range Set-
ting
Write/
Read
Sets the input range.
−
10 to 10 V: 0
0 to 5 V: 1
0 to 10 V: 2
4 to 20 mA: 3
1 to 5 V: 7
0 to 20 mA: 8
Write:
10 hex
Read:
0E hex
8F hex 01 to 04
hex
*1
66 hex
*2
8E hex
*3
1 byte
1 byte
Analog Sta-
tus Flag
Read
Read Reads the status of the
Analog Status Flags.
LL = 0; L = 1;
Pass signal = 2; H = 3;
HH = 4; Valley shot = 5;
Top shot = 6;
Off-wire detection = 7
0E hex
8F hex 01 to 40
hex
*1
69 hex
*2
91 hex
*3
1 byte
Analog
Data 1 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 1.
Analog input value: 0;
Peak value: 1;
Bottom value: 2;
Top value: 3;
Valley value: 4;
Rate of change value: 5
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6B hex
*2
93 hex
*3
1 byte
1 byte
Analog
Data 2 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 2.
Analog input value: 0;
Peak value: 1;
Bottom value: 2;
Top value: 3;
Valley value: 4;
Rate of change value: 5
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6C hex
*2
94 hex
*3
1 byte
1 byte
Function
Setting
Write/
Read
Sets each function.
Bit status:
ON: Enabled,
OFF: Disabled
Moving average: 0;
Scaling: 1;
Peak/bottom hold: 2;
Top/valley hold: 3;
Comparator: 4;
Cumulative counter: 5;
Rate of change: 6
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6D hex
*2
95 hex
1 byte
1 byte
Scaling
Type Set-
ting
Write/
Read
Default scaling: 0:
User scaling: 1
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6E hex
*2
96 hex
1 byte
1 byte
Scaling
Point 1 Set-
ting
Write/
Read
Sets an analog value as
the 0% value for user
scaling.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6F hex
*2
97 hex
*3
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Scaling
Point 2 Set-
ting
Write/
Read
Sets an analog value as
the 100% value for user
scaling.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
70 hex
*2
98 hex
*3
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Attribute ID
Data
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......