196
Temperature Input Units
Section 6-4
■
Timing for Setting Data
■
Setting Hysteresis (Example: DeviceNet Configurator)
1,2,3...
1. Input the value for hysteresis in the
Hysteresis
Field in the
Top/Valley
Tab
in the
Function Choice
Area.
2. Return to the
General
Tab Page, click the
Download
Button, and then
click the
Reset
Button to reset the Unit.
3. Click the
OK
Button to exit.
Note
The hysteresis value set for the top/valley hold function is also used by the
comparator function.
Temperature input value
Set hysteresis value
×
2
Valley hold value
Top/Valley Detection
Timing Flag
Delay