325
Explicit Messages
Appendix A
Captured
Counter
Value
Read
Reads the last
captured counter
value.
0E hex
8E hex 01 to 40
hex
*1
88 hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Counter
Frequency
Read
Reads the
present counter
frequency
(speed).
0E hex
8E hex 01 to 40
hex
*1
89 hex
---
4 bytes
Range of values:
−
100,000 to
100,000
Lower Limit
of Range 0
Read
Reads the
present lower
limit of compari-
son range 0.
*3
0E hex
8E hex 01 to 40
hex
*1
8B hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Upper Limit
of Range 0
Read
Reads the
present upper
limit of range 0.
*3
0E hex
8E hex 01 to 40
hex
*1
8C hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Lower Limit
of Range 1
Read
Reads the
present lower
limit of range 1.
*3
0E hex
8E hex 01 to 40
hex
*1
8D hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Upper Limit
of Range 1
Read
Reads the
present upper
limit of range 1.
*3
0E hex
8E hex 01 to 40
hex
*1
8E hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Preset
Value
Read
Reads the
present preset
value.
0E hex
8E hex
01 to 40
hex
*1
8F hex
---
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
Write
Writes the preset
value.
10 hex
8E hex
01 to 40
hex
*1
8F hex
4 bytes
Range of values:
−
2,147,483,648 to
2,147,483,647
---
Counter
Input Mode
Read
Reads the
present counter
input mode.
0E hex
8E hex
01 to 40
hex
*1
90 hex
---
1 byte
00 hex: Phase dif-
ferential
×
1
01 hex: Phase dif-
ferential
×
2
02 hex: Phase dif-
ferential
×
4
03 hex:
Pulse/direction
04 hex: Up/down
Write
Writes the
counter input
mode.
10 hex
8E hex
01 to 40
hex
*1
90 hex
1 byte
00 hex: Phase dif-
ferential
×
1
01 hex: Phase dif-
ferential
×
2
02 hex: Phase dif-
ferential
×
4
03 hex: Pulse
/direction
04 hex: Up/down
---
Explicit
message
Read/
write
Function Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......