216
Temperature Input Units
Section 6-4
7. Select the Tab Page for the input that will be adjusted and click the
Adjust-
ment
Button to open the Adjustment Window.
8. Adjust the lower limit value (lower adjusting value). Input 0 mV from the ref-
erence voltage/current generator (STV) to the Temperature Input Termi-
nal’s input terminals. Wait at least 1 minute for the input to stabilize.
9. Click the
Fix lower adjusting Value
Button. The lower limit adjustment
value will be stored in the Unit.
10. Adjust the upper limit value (upper adjusting value). Input the upper limit
voltage from the reference voltage/current generator to the input terminals
of the input to be adjusted. Refer to the following table for the appropriate
voltage. Wait at least 1 minute for the input to stabilize.
Input type
Input voltage
K (
−
200 to 1300
°
C)
50 mV
K (0.0 to 500.0
°
C)
20 mV
J (
−
100 to 850
°
C)
50 mV
J (0.0 to 400.0
°
C)
20 mV
T
20 mV
L (
−
100 to 850
°
C)
50 mV
L (0.0 to 400.0
°
C)
20 mV
U
20 mV
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......