206
Temperature Input Units
Section 6-4
3. The comparison result will be read to a precision of 0.01, regardless of the
setting.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3. Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the
Data comparison between channels
Tab.
5. Double-click the
Calculation Data1
or
Calculation Data2
header cell to
open the Edit Calculation Data Window. Select the two temperature inputs
to be compared from the pull-down menus in the
Calculation Data1
and
Calculation Data2
Fields. The comparison will be calculated by subtracting
Calculation Data2
from
Calculation Data1.
Set a threshold value in the
Threshold Value
Field. Always set the threshold value to a precision of
0.01. For example, when setting 10
°
C, input 1000 for 10.00
°
C.
540
°
C
5
8
0
°
C?
Temperature difference
with device A is large.
Is there an error?
Device A
Device B
Compare
Temperature
Input Unit
Detect temperature differences
between inputs.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......