11. Click the
Fix upper adjusting Value
Button. The upper limit adjustment
value will be stored in the Unit.
12. To check whether the user adjustment values have been accepted and the
Unit is operating with adjustment values different from the factory defaults,
click the right mouse button over the Slave icon and select
Maintenance
Information
to open the Maintenance Information Window.
Select the Tab Page for the input that was adjusted. If there is a check in
the
User Adjustment
Box (bottom right box), the Unit is operating with us-
er-set adjustment values.
Note
1. When checking whether or not the user adjustment values have been set
correctly, always refresh the data by clicking the
Update
Button in the
Maintenance Information Window’s
General
Tab or uploading the settings
again. For details on the Maintenance Information Window, refer to
Maintenance Information Window
.
2. If the correct reference voltage was not input, the adjustment values may
not be accepted.
■
Adjusting the GRT1-TS2T’s Bias Compensation Value
1,2,3...
1. Remove the wiring for upper/lower limit compensation and wiring the Unit
as shown for bias compensation.
2. After completing wiring, wait until the temperature data stabilizes (i.e., until
there is no change in the temperature data for at least 20 minutes). De-
pending on the system setup, this may take over 60 minutes. When the
temperature data is stable, click the
Fix Bias adjusting Value
Button.
N
50 mV
PL2
50 mV
Input type
Input voltage
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......