![background image](http://html1.mh-extra.com/html/omron/smartslice-grt1-drt/smartslice-grt1-drt_operation-manual_742293192.webp)
172
Temperature Input Units
Section 6-4
Note
The ERR indicator will not light or flash if input error detection has
been disabled (i.e., if the input error detection disable setting has
been set to disable detection).
An input error occurs when the input value exceeds the convertible tempera-
ture range. Disconnections and cold junction compensation errors are treated
as input errors. Refer to
Convertible Temperature Ranges
on page 175 for
more information. For information on LED indicator troubleshooting, refer to
9-2 LED Indicators and Error Processing
for details.
Setting the Input Type
The input type can be set using the DIP switch or the Setting Tool.
Setting with the DIP
Switch
Each pin is set according to the following table.
Note
If the settings are incorrect, the TS Indicator will flash red and the Unit will not
operate. In this case, make the settings again and turn the power supply OFF
and ON.
ERR1
Red
Lit
Error
An input error has occurred in
input 1.
An error has occurred in the cold
junction compensator
(GRT1-TS2T only).
---
Not lit Normal status
There is no input error for input 1.
Name
Color
Status
Meaning
Pin
Setting
Specifications
1
Select the input type (i.e., input
range). Make the input type set-
ting using the combinations in the
following table.
Default setting: OFF
2
3
Select a
°
C or
°
F display.
OFF:
°
C conversion
ON:
°
F conversion
Both inputs are set together and cannot be
set individually. The default setting is OFF.
The selection of
°
C or
°
F display cannot be
set with the Setting Tool.
4
Select the input type setting
method. Select either setting with
DIP switch or with the Setting
Tool.
OFF: Set with the Setting Tool.
ON: Set with DIP switch.
When the input type is set with the DIP
switch, all inputs must be set to the same
input type. To set different input types, use
the Setting Tool to make the settings.
Default setting: OFF
1
2
3
4
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......