![background image](http://html1.mh-extra.com/html/omron/smartslice-grt1-drt/smartslice-grt1-drt_operation-manual_742293248.webp)
228
Status Areas
Section 7-2
Warning Status Area
The Counter Unit’s or Positioning Unit’s Warning Status Area contains the fol-
lowing 16 bits. The Warning Status Area provides notification of minor errors
in the Unit. When any of the flags turns ON, bit 2 of the Communications
Unit’s Status Flags is turned ON and that information is transmitted to the
Master.
Alarm Status Area
The Counter Unit’s or Positioning Unit’s alarm status area contains the follow-
ing 16 bits.The Alarm Status Area provides notification of serious errors in the
Unit. The flags indicate non-fatal errors in the Unit. When any of these flags
turns ON, bit 3 of the Communications Unit’s Status Flags is turned ON and
that information is transmitted to the Master.
Bit
Content
Description
0 Reserved
---
1
Reserved
---
2
Reserved
---
3
Unit Maintenance Flag
OFF: Normal
ON: Error (Over threshold or
87672 hours)
Monitors the power ON time warning
value set for the Unit Conduction Time
Monitor function.
Also monitors whether 87672 hours (10
years) have elapsed.
4
Reserved
---
5
Reserved
---
6
Reserved
---
7
Reserved
---
8
Reserved
---
9
Connected Device Maintenance
Flag
OFF: Within range (all points
below set value)
ON: Out-of-range (one or more
points exceeded set value)
Monitors the warning value set for the
Contact Operation Counter or Total ON
Time Monitor function.
10
Reserved
---
11
Reserved
---
12
Reserved
---
13
Reserved
---
14
Reserved
---
15
Reserved
---
Bit
Content
Description
0 Reserved
---
1
EEPROM Data Error Flag
OFF: Normal
ON: Error occurred
2
Reserved
---
3
Reserved
---
4
Reserved
---
5
Reserved
---
6
Reserved
---
7
Reserved
---
8
I/O Power Supply Status Flag
OFF: I/O power supply ON
ON: I/O power supply OFF
9
Reserved
---
10
Reserved
---
11
Reserved
---
12
Reserved
---
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......