199
Temperature Input Units
Section 6-4
Note
If the sampling cycle is set to a small value, the rate of change will be sensi-
tive to small changes. If the temperature data is subject to minute fluctuations,
and the sampling cycle is shorter than the cycle of fluctuation, the fluctuation
will be regarded as the rate of change. To prevent this occurring, use moving
average processing, which will set a longer sampling cycle.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1. In the Network Configuration Window, for the Slice I/O Terminal, dou-
ble-click the icon of the Slice I/O Terminal that is to be set. Alternatively,
right-click the icon and select
Parameters - Edit
. The Edit Device Param-
eters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3. Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
0
Temperature
input value
Rate of
change
Derivative data
Temperature data
Time
Fluctuation in the
temperature input value
Short sampling cycle
Desired gradient
Long sampling cycle
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......