223
Temperature Input Units
Section 6-4
9. Click the
Fix Lower Adjusting Value
Button. The lower limit adjustment
value will be stored in the Unit.
10. Adjust the upper limit value (upper adjusting value). Refer to the following
table for the appropriate resistance to input from the six-dial resistance box
to the Temperature Input Unit’s input terminals. Wait at least 1 minute for
the input to stabilize.
11. Click the
Fix Upper Adjusting Value
Button. The upper limit adjustment
value will be stored in the Unit.
12. If it is necessary to restore the upper and lower limit adjustment values to
the default settings, click the
Default Setting
Button. The settings will be
returned to the factory settings.
Model
Input type
Upper limit
adjustment input
resistance
GRT1-TS2P
PT100 (
−
200 to 850
°
C)
390
Ω
PT100 (
−
200 to 200
°
C)
180
Ω
GRT1-TS2PK
PT1000 (
−
200 to 850
°
C)
3,900
Ω
PT1000 (
−
200 to 200
°
C)
1,800
Ω
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......