![background image](http://html1.mh-extra.com/html/omron/smartslice-grt1-drt/smartslice-grt1-drt_operation-manual_742293262.webp)
242
GRT1-CT1(-1) Counter Units
Section 7-4
7-4-4
Functions and Settings
The following functions are the same as those for the Digital I/O Units. Refer
to the sections given below for details.
Setting Special
Counter Unit
Functions
Counter Unit functions are set using the Edit Unit Parameters Window. The
procedure for accessing the Edit Unit Parameters Windows depends on the
Support Software that is being used. The procedure for DeviceNet Configura-
tor (version 2.43 or higher) is given below as an example.
m+2
(contin-
ued)
07
Overflow Flag
This flag will turn ON if the count value overflows. Counting will stop with the count value at the
upper limit. The upper limit is 2,147,483,647. To restart counting, preset or reset the counter value.
This flag will turn OFF when counting restarts.
08
Counter Operation Flag
This flag shows the status of counter operation. The counter operation can be controlled by the Gate
Control Bit (bit 08 of word n+2).
OFF: Stopped.
ON: In progress.
09
Capture Command Completed Flag
This flag turns ON when the Capture Command has been completed (triggered by the Capture
Command Bit, bit 09 of word n+2).This flag will turn OFF when the Capture Command Bit is reset.
10
Preset Command Completed Flag
This flag turns ON when the Preset Command has been completed (triggered by the Preset Com-
mand Bit, bit 10 of word n+2). This flag will turn OFF when the Preset Command Bit is reset.
11
Reset Command Completed Flag
This flag turns ON when the Reset Command has been completed (triggered by the Reset Com-
mand Bit, bit 11 of word n+2). This flag will turn OFF when the Reset Command Bit is reset.
12
Digital Input (IN) Status Flag
This flag shows the present status of the digital input.
OFF: Low (OFF)
ON: High (ON)
13
Reserved.
14
Digital Output Status Flag
This flag shows the present status of the digital output.
OFF: Low (OFF)
ON: High (ON)
15
Reserved.
Word
Bits
Definition
Function
Reference
I/O Power Supply Monitor
4-4-1 I/O Power Supply Monitor
Contact Operation Counter
4-4-4 Contact Operation Counter
Total ON Monitor Time
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......