100
Analog Input Units
Section 5-4
Performance Specifications
Storage temperature
–25 to 65°C (with no icing or condensation)
Mounting
35-mm DIN Track mounting
Item
Specifications
Voltage input
Current input
Input points
2 points (inputs 0 to 1)
Input signal range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
Input range setting method
• DIP switch: Inputs 0 and 1 share the same setting.
• Setting Tool: Inputs 0 to 1 can be set separately.
Maximum signal input
±
15 V
±
30 mA
Input impedance
1 M
Ω
min. Approximately
250
Ω
Resolution
1/6,000 (full scale)
Overall accuracy
25°C
±
0.3% FS
±
0.4% FS
–10 to 55°C
±
0.6% FS
±
0.8% FS
Analog conversion cycle
2 ms max./2 points (when math operations are not used)
AD conversion data
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
AD conversion range:
±
5% FS of the above data ranges.
Isolation method
Photocoupler isolation (between input and communications lines)
No isolation between input signal wires
I/O connection method
Screwless Terminal block
Item
Specifications
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......