![background image](http://html1.mh-extra.com/html/omron/smartslice-grt1-drt/smartslice-grt1-drt_operation-manual_742293326.webp)
306
Explicit Messages
Appendix A
Explicit Messages for Digital I/O Units
Setting and Monitoring Input Terminals
Explicit
message
Read/
write
Function Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read
Reads the input’s
monitor mode for
maintenance infor-
mation.
0E hex
8E hex
01 to 40
hex
*1
74 hex
---
4 bytes
0: Total ON
time mode
1: Contact oper-
ation counter
mode
The mode is
read for inputs 0
to 32.
*10
Write
Writes the input’s
monitor mode for
maintenance infor-
mation.
10 hex
8E hex
01 to 40
hex
*1
74 hex
4 bytes
0: Total ON
time mode
1: Contact oper-
ation counter
mode
The mode is set
for inputs 0 to
32.
*10
---
Set Value
of Input
Mainte-
nance
Counter
Read
Reads the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) the input (0 to
3, or 0 to 7 for an
Eight-input Unit)
specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
66 hex
*2
69 hex
*3
6C hex
*4
6F hex
*5
9C hex
*6
9F hex
*7
A2 hex
*8
A5 hex
*9
---
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Write
Writes the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) for the input
(0 to 3, or 0 to 7 for
an Eight-input Unit)
specified by the
Attribute ID.
10 hex
8E hex
01 to 40
hex
*1
66 hex
*2
69 hex
*3
6C hex
*4
6F hex
*5
9C hex
*6
9F hex
*7
A2 hex
*8
A5 hex
*9
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
---
Read Input
Mainte-
nance
Counter
Read
Reads the total ON
time (unit: s) or
number of contact
operations (unit:
operations) for the
input (0 to 3, or 0 to
7 for an Eight-input
Unit) specified by
the Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
65 hex
*2
68 hex
*3
6B hex
*4
6E hex
*5
9B hex
*6
9E hex
*7
A1 hex
*8
A4 hex
*9
---
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......