RP0177-2000
6
NACE International
Table 1: Maximum 60 Hz Fault Currents—Grounding Cables
(A)
Cable Size
Fault Time
rms Amperes
Cable Size
Fault Time
rms Amperes
AWG
(B)
Cycles
Copper
Aluminum
AWG
Cycles
Copper
Aluminum
1
15
10,550
6,500
3/0
15
26,500
16,500
30
7,500
4,600
30
18,500
16,500
60
5,300
3,200
60
13,000
8,000
1/0
15
16,500
10,500
4/0
15
30,000
21,000
30
11,500
7,500
30
21,000
15,000
60
8,000
5,300
60
15,000
10,000
2/0
15
21,000
13,000
250 MCM
15
35,000
25,000
30
15,000
9,000
30
25,000
17,500
60
10,000
6,500
(A)
Based on 30°C (86
q
F) ambient and a total temperature of 175°C (347
q
F) established by Insulated Cable Engineers
Association (ICEA)
(2)
for short-circuit characteristic calculations for power cables. Values are approximately 58% of fusing
currents.
(B)
American Wire Gauge (AWG)
where C = average specific heat in BTU/([lb][
q
F])of
annealed soft-drawn copper over the temperature
range T
1
to T
2
, M = mass of copper in pounds, T
1
and T
2
= initial and final temperatures respectively in
degrees Fahrenheit. Figure 1 was developed using C
= 0.104 BTU/([lb][
q
F]), T
1
= 68°F, and T
2
= 1,300°F.
(3)
Typical resistance values are shown in Table 2.
4.9 Isolating Joints
4.9.1 Isolating joints may be installed to divide the
structure into shorter electrical sections or to isolate
a section adjacent to an AC power system from the
remainder of the structure. Isolating joints installed
in areas where a possibility of damage exists
because of induced AC potentials or fault currents
should have lightning arresters, polarization cells,
electrolytic grounding cells, or similar protective
devices installed across the joints. The threshold
voltage characteristics of lightning arresters should
be considered, and installation should include
personnel protection such as dead-front construction.
(The AC and DC isolation provided by isolating joints
is not provided during the conducting mode of some
protective devices.)
4.10 Electrolytic Grounding Cells, Polarization Cells, and
Other Devices
4.10.1 The coordinated selection and installation of
electrolytic grounding cells, polarization cells (2.5-V
DC maximum threshold), or other devices between
the affected structure and suitable grounds should be
considered where arcing and induced AC potentials
could develop. These devices may eliminate or
greatly reduce the induced potentials resulting during
normal operation or surge conditions and also reduce
the possibility of arcing and structure puncture.
4.10.2 Where electrolytic grounding cells,
polarization cells (2.5-V DC maximum threshold), or
other devices are used, they should be properly
sized, spaced, and physically secured in a manner
that safely conducts the maximum amount of
anticipated surge current. Cables connecting these
devices to the structures shall be properly sized as
described in Paragraph 4.8.1. Cables should be kept
as short and straight as possible. An adequately
sized shunting circuit should be provided to permit
electrical isolation of the grounding device during
testing and maintenance.
4.11
Lightning Arresters and Metal Oxide Varistors
(MOVs)
4.11.1
Lightning arresters and MOVs may be
used between structures and across pipeline
electrical isolating devices. However, one restriction
to the use of lightning arresters is that a potential
difference has to develop before the arrester
conducts. With certain types of arresters, this
potential may be high enough to become hazardous
to people coming in contact with the arrester. When
lightning arresters are used, they must be connected
to the structure through adequately sized cables as
described in Paragraph 4.8.1. Lightning arresters
should always be provided with a reliable, low-
resistance ground connection. They should be
located close to the structure being protected and
have a short, straight ground path. An adequately
____________________________
(2)
Insulated Cable Engineers Association (ICEA), P.O. Box 440, South Yarmouth, MA 02664.
(3)
To calculate Q using metric units:
1. Find C (average specific heat) in “(cal/g)(ºC)” or “BTU/([lb][
q
F])” from handbook tables.
2. Substitute M (mass) with “0.002205 x M
(g)
” where M
(g)
= mass of copper in grams.
3. Substitute T
1
= (
q
C
1
+ 17.78)(1.8) and T
2
= (
q
C
2
+ 17.78)(1.8).
Summary of Contents for CP 1
Page 1: ...CP 1 Cathodic Protection Tester Course Manual February 2005 NACE International 2000 ...
Page 265: ......
Page 266: ......
Page 267: ......
Page 268: ......
Page 301: ...RP0169 2002 32 NACE International ISBN 1 57590 035 1 ...
Page 535: ...TM0101 2001 24 NACE International ISBN 1 57590 137 4 ...