RP0200-2000
NACE International
9
If operator data and experience indicate that it is
appropriate, a difference in potential as small as 20 mV,
or as large as 200 mV, may be considered a criterion
indicating that the casing under test requires further
examination.
2. Internal Resistance Test
Purpose
This technique may indicate whether direct metal-to-
metal contact exists between a carrier pipe and a casing
pipe by measuring electrical resistance.
Only qualified cathodic protection personnel should
analyze the results when this test is run on a buried/tied-
in pipeline.
Procedure
This procedure requires an appropriate wet-cell battery
(e.g., car battery), a properly rated ammeter or shunt, a
properly rated resistor, sufficient lead wire, clamps, and a
multimeter. See cautionary note following Figure B2.
1.
The pipe-to-casing potential shall be measured at
terminals T1 and T2. See Figure B2.
2.
One battery lead shall be attached to a casing test
lead at T3 (if no test lead is available then the casing vent
[T1] may be used). The other lead shall be connected in
series with the ammeter to the carrier pipe at T4.
3. A constant current shall be applied between
terminals T3 and T4. The current (I) shall be measured
in amperes.
4.
The pipe-to-casing potential shall be measured
between terminals T1 and T2 with the current applied.
VOLT
METER
CARRIER PIPE
CASING
GROUND LEVEL
T1 T2
T3
T4
+
-
VENT PIPE
BATTERY
+
-
AM-
METER
VARIABLE RESISTOR
VENT PIPE
TEST LEAD
TEST LEAD
FIGURE B2: Internal Resistance Test
CAUTION: It is very dangerous to short the leads of a wet-cell battery together. The above procedure may produce a direct
short if a metal-to-metal contact exists between the carrier pipe and the casing. Therefore, only dry-cell batteries or a wet-
cell battery with a properly rated resistor installed in series shall be used. Maximum battery output shall be limited to 10 A.
Note: A four-pin soil resistivity meter may replace the battery, voltmeter, and ammeter shown in Figure B2 so that the
resistance may be read directly. If a four-pin soil resistivity meter is used, the locations of the test leads are the same as
those shown in Figure B2. C1 is connected to T3, P1 to T1, P2 to T2, and C2 to T4.
U/S End
D/S End
Summary of Contents for CP 1
Page 1: ...CP 1 Cathodic Protection Tester Course Manual February 2005 NACE International 2000 ...
Page 265: ......
Page 266: ......
Page 267: ......
Page 268: ......
Page 301: ...RP0169 2002 32 NACE International ISBN 1 57590 035 1 ...
Page 535: ...TM0101 2001 24 NACE International ISBN 1 57590 137 4 ...