Installing C.P. Components
8:23
CP 1 – Cathodic Protection Tester Course Manual
©
NACE International, 2000
07/01/04
Earth
Backfill
Header Cable
to Other Anodes
and Power
Source
Insulated
Cable
Connection
Anode
Backfill
Anode
Augered
Hole
10’
1’
5’
1’
2’
Figure 8.19 Vertical Impressed Current Anode Showing Typical
Dimensions
Horizontal Anode Installation
The first step in a horizontal installation is the installation of the anodes.
This is done in a manner similar to that for a vertical anode installation. The
anode installation depends on the spacing of the anodes. If the spacing is
more than 10 feet, it is usually best to excavate a separate hole for each
anode. With closer spacing, it is usually more economical to dig one long
trench for both the header cable and the anodes.
Bare or prepackaged anodes may be used. They are installed, using coke
breeze backfill, in a manner similar to that explained above for vertical
anodes. Again, be certain to follow the design drawings and specifications
during the installation.
Figure 8.20 illustrates a typical horizontal installation.