RP0196-2004
NACE International
5
4.3.5.3 The galvanic anode utilization factor when
calculating life shall not exceed 85%.
(A)
Corrosion potential varies with water chemistry.
(B)
CSE = Saturated copper/copper sulfate reference electrode.
(C)
Consumption rate is dependent on water chemistry and anode current density.
(D)
ASTM International, 100 Barr Harbor Dr., West Conshohocken, PA 19428-2959.
(E)
ASTM B 843 (latest revision), "Standard Specification for Magnesium Alloy Anodes for Cathodic Protection" (West Conshohocken, PA:
ASTM).
(F)
ASTM B 418 (latest revision), "Standard Specification for Cast and Wrought Galvanic Zinc Anodes" (West Conshohocken, PA: ASTM).
4.3.6 Other
4.3.6.1 The preferred method of cable connection
to the tank is by welding or thermite welding. If
other connection methods, such as bolting,
clamping, etc., are used, they must be secure. All
electrical connections must be protected against
corrosion.
4.3.6.2 All cable connections to the galvanic
anodes shall be made to the core material by
silver solder and subsequently coated.
4.3.6.3 All immersed cable-to-cable connections
shall be made by high-strength compression
connector or welding.
4.3.6.4 All cables located inside the tank shall be
rated for use in submerged conditions.
4.3.6.5 For bolted and riveted tanks, electrical
continuity of all joining components must be
achieved if these components are to receive CP.
________________________________________________________________________
Section 5: Installation of Galvanic Anode CP Systems
5.1 Introduction
5.1.1 This section outlines installation techniques for
galvanic anode CP systems that protect water storage
tanks when design considerations recommended in
Section 4 have been followed.
5.2 Construction Specifications
5.2.1 All construction work on galvanic anode CP
systems should be in accordance with construction
drawings and specifications.
5.3 Construction Supervision
5.3.1 All construction work should be performed by, or
under the direction of, a person who is qualified by
experience in the installation of galvanic anode CP
systems in water storage tanks, and who should verify
TABLE 1
TYPICAL GALVANIC ANODE MATERIALS AND CHARACTERISTICS
TYPE
ALLOY
NOMINAL
CORROSION
POTENTIAL
(A)
mV vs. CSE
(B)
NOMINAL
CONSUMPTION
RATE
(C)
kg/A-yr
Mg
ASTM
(D)
B 843
(E)
Mg/Mn
M1C
-1,750
8
Mg/Al/Zn
AZ31B
-1,550
8
Mg/Al/Zn
AZ63B
-1,550
8
Zn
ASTM B 418
(F)
Low Fe
Type II
-1,100
12
Summary of Contents for CP 1
Page 1: ...CP 1 Cathodic Protection Tester Course Manual February 2005 NACE International 2000 ...
Page 265: ......
Page 266: ......
Page 267: ......
Page 268: ......
Page 301: ...RP0169 2002 32 NACE International ISBN 1 57590 035 1 ...
Page 535: ...TM0101 2001 24 NACE International ISBN 1 57590 137 4 ...