408
-
'12 • PAC-T-174
E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
Is the
power transistor
module OK?
(inverter PCB anomaly)
NO
Is the
inverter output OK?
(Check by inverter
checker)
Does it start?
NO
YES
YES
YES
YES
Note(1) Several times restarting
may recover it, because liquid
refrigerant migrated in the
compressor could be discharged
from the compressor.
After power OFF, turn
SW10-4 of inverter
PCB ON and connect
the inverter checker.
Then power ON again.
Try to restart several times
Is it model 200
or 250?
From previous page
Replace inverter PCB
* For model 200 and 250,
replace power transistor
as well.
Replace inverter PCB
* For model 200 and 250,
replace power transistor
as well.
Replace compressor
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
5 times flash
Keeps flashing
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Stays OFF or 4 times flash
Yellow LED Red LED Green LED
Compressor startup failure (2/2)
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...