331
-
'12 • PAC-T-174
(iv) Display sequence of error codes or inspection indicator lamps
■
Occurrence of one kind of error
Displays are shown respectively according to errors.
■
Occurrence of plural kinds of error
Section
Category of display
Error code on remote
controller
• Displays the error of higher priority (When plural errors are persisting)
• Displays the present errors. (When a new error has occurred after the former error was reset.)
Red LED on indoor
control PCB
Red LED on outdoor
control PCB
■
Error detecting timing
Section
Error description
Error code
Error detecting timing
Indoor
Drain trouble (Float switch
activated)
Whenever float switch is activated after 30 second had past since
power ON.
Communication error at
initial operation
“
WAIT
” No communication between indoor and outdoor units is
established at initial operation.
Remote controller
communication circuit error
Communication between indoor unit and remote controller is
interrupted for mote than 2 minutes continuously after initial
communication was established.
Communication error during
operation
Communication between indoor and outdoor units is interrupted
for mote than 2 minutes continuously after initial communication
was established.
Excessive number of
connected indoor units by
controlling with one remote
controller
Whenever excessively connected indoor units is detected after
power ON.
Return air temperature
thermistor anomaly
-50 (-45) °C or lower is detected for 5 (15) seconds continuously
within 60 minutes after initial detection of this anomalous
temperature.
Indoor heat exchanger
temperature thermistor
anomaly
-50 (-28) °C or lower is detected for 5 (15) seconds continuously
within 60 minutes after initial detection of this anomalous temperature.
Or 70°C or higher is detected for 5 seconds continuously. (SRK
series removes)
Outdoor
Outdoor air temperature
thermistor anomaly
-45°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
Or -45°C or higher is detected for 5 seconds continuously within
20 seconds after compressor ON.
Outdoor heat exchanger
temperature thermistor
anomaly
-50°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
Or -50°C or lower is detected for 5 seconds continuously within
20 seconds after compressor ON.
Discharge pipe temperature
thermistor anomaly
-10°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
Suction pipe temperature
thermistor anomaly
-50°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
Low pressure sensor anomaly
0V or lower or 3.49V or higher is detected for 5 seconds
continuously 3 times within 40 minutes after initial detection of
this anomalous pressure.
Underneath temperature
thermistor anomaly
-50°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
Note (1) Value in ( ) are for the SRK series.
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...