-
481
-
'12 • PAC-T-174
Wood screw
Holder for remote controller
Installation tips for the remote controller holder
Adjust and keep the holder upright
Tighten the screw to the end to avoid scratching the remote controller.
DO NOT attach the holder on plaster wall.
Installation of the controller holder
How to insert batteries
1
Detach the back lid.
2
Insert the batteries. (two AAA batteries)
3
Reattach the back lid.
Control plural indoor units with one remote controller
Up to 16 indoor units can be connected.
1
Connect the XY terminal with 2-core wire. As for the size, refer to the following note.
2
For Single packaged air conditioner series, set the indoor unit address with SW2 on the indoor
unit PCB from [0] to [F] so as not to duplicate.
Restrictions on the thickness and length of wire
(Maximun total extension 600m.)
Within 100m x 0.3 mm
2
Within 200m x 0.5 mm
2
Within 300m x 0.75mm
2
Within 400m x 1.25mm
2
Within 600m x 2.0 mm
2
Standard
Master/Slave setting when using plural remote controllers
Terminal block
Remote controller
3
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the indoor
unit PCB from [000] to [127] so as not to duplicate.
Up to two receivers can be installed in one indoor unit group.
When two receivers are used, it is necessary for a receiver to turn OFF SW2 on the receiver PCB
to set it as slave.
Note
Caution
How to disable the Auto mode operation
VRF series (except heat recovery 3-pipe systems) cannot be operated
in Auto mode.
Make sure to set the remote controller for the models so as not to be
able to choose Auto mode.
Pressing ACL switch with MODE button kept pressing or inserting
the batteries with pressing MODE button will make auto mode
operation.
When the batteries are removed, the setting will return to the
default setting (Auto mode is valid).
Instruct the customer to set the mentioned above when
replacing the batteries. (How to set is also mentioned in
the user’s manual attached on the air conditioner.)
Cooling test run operation
After safety confirmation, turn on the power.
Transmit a cooling operation command with wireless remote controller, while the backup button on
the receiver is pressed.
If the backup button on the receiver is pressed during a test run, it will end the test run.
If you cannot operate the unit properly during a test run, please check by consulting with inspection
guides on the wiring diagram of outdoor units.
How to read the two-digit display
On the receiver of a wireless kit, a two-digit (7-segment) display is provided.
(1) An indication will be displayed for one hour after power on.
(2) An indication will be displayed for 3.5 seconds after transmitting a “STOP” command from the
wireless remote controller or the operation of the backup button to stop the unit.
(3) An indication appearing in (1) or (2) above will go off as soon as the unit starts operation.
(4) When there are no error records to indicate, addresses of all the connected units are displayed.
(5) When there are some error records remaining, the error records are displayed.
(6) Error records can be cleared by transmitting a “STOP” command from the wireless remote
controller, while the backup button is pressed.
Backup button
A Backup button is provided on the receiver.
Even when the operation from the wireless
remote controller is not possible (due to flat
batteries, controller lost, or controller failure),
still it possible to operate as temporary means.
Press the button directly when operating it.
(1) The air conditioner starts the operation with
the condition of Auto mode, 23
˚
C of set
point, High fan speed and horizontal louver
position.
(2) The air conditioner stops the operation when
the button is pressed when in operation.
Remote controller
Wireless remote controller’s operable area
1
Standard reachable area of the signal
[condition] Illuminance at the receiver: 300lux
(when no lighting is installed within 1m of the receiver in an ordinary office.)
2
Correlation between illuminance at the receiver
and reachable area of the signal in a plain view.
The drawing in the right shows the
correlation between the reachable area
of the signal and illuminance at the
receiver when the remote controller is
operated at 1m high under the
condition of ceiling height of 2.4m.
The receivable area of the
signal when the illuminance
at the receiver is 300lux
The receivable area of the
signal when the illuminance at
the receiver is 600lux
3
Installation tips when several receivers are installed close
Minimum distance between the indoor units which can avoid cross communication is 5m
under the condition of 300lux of illuminance at the receiver.
(When no lighting is installed within 1m of the receiver in an ordinary office )
Caution
DO NOT install it on the following places
1. Places exposed to direct sunlight
2. Places near heat devices
3. High humidity places
Ensure the correct
polarity when
inserting.
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address ( F )
Receiver
(For the method of switching, please see Setting on site in the section of
2
How to install the receiver
in this manual.)
Auto mode operation setting
4. Hot surface or cold surface enough to generate
condensation
5. Places exposed to oil mist or steam directly.
6. Uneven surface
Reachable area of the signal
Backup button
Ceiling surface
4m
3m
2m
1m
0
1m
2m
3m
4m
1
m
1
.4
m
2
.4
m
4m
4m
3m
3m
2m
2m
1m
1m
PJA012D758
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...