349
-
'12 • PAC-T-174
●
DIP switch setting list (Outdoor unit)
(1) Control PCB
* Default setting
SW1
OFF
JSW1-1
JSW1-2
JSW1-3
JSW1-4
SW3-1
Normal*/Cold region
OFF
SW3-2
Normal*/Snow protection
OFF
SW3-3
OFF
SW3-4
OFF
SW4-1
ON
SW4-2
See table 1
SW4-3
OFF
SW4-4
OFF
SW5-1
OFF
SW5-2
OFF
SW5-3
OFF
SW5-4
OFF
Keep OFF
Keep OFF
Keep OFF
Keep OFF
Keep OFF
Keep OFF
Reserved
Overseas
See table 1
Model selection
3-phase/Single phase
As per model
Model selection
Domestic/Overseas*
Normal
Test run mode
Cooling*/Heating
Cooling
Test run SW
Normal*/Test run
Normal
Snow protection control
Normal
Default setting
Model selection
Defrost condition
Normal*/Pump down
Normal
As per model
See table 1
Switches
Description
Remarks
Pump down operation
Reserved
Reserved
Reserved
Reserved
Reserved
* 3-phase: OFF/Single phase: ON
Table 1: Outdoor unit model selection with JSW1-1-JSW1-4 and SW4-1-SW4-2
0: OFF 1:ON
100VN 100VS 125VN 125VS 140VN 140VS 200VS 250VS
JSW1-1
0
0
1
1
0
0
1
0
JSW1-2
0
0
0
0
1
1
1
0
JSW1-3
0
0
0
0
0
0
0
1
JSW1-4
0
0
0
0
0
0
0
0
SW4-1
1
1
1
1
1
1
1
1
SW4-2*
1
0
1
0
1
0
0
0
JSW11-2
JSW11-1
JSW11-4
JSW11-3
JSW10-4
JSW10-2
JSW10-3
Switches
JSW10-1
(2) Inverter PCB
OFF
OFF
OFF
*
OFF
*
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
100, 125, 140VN
100, 125, 140VS
Single phase models
3-phase models
SW2-2
OFF
200,250VS
3-phase models
OFF
SW2-1
ON
OFF
SW2-4
OFF
SW2-3
OFF
SW1-4
OFF
SW1-2
OFF
SW1-3
Switches
SW1-1
*
When checking inverter PCB of FDC100-140 models with inverter checker, turn JSW10-4 ON.
(Regarding the checking method of inverter PCB with inverter checker, refer to page 346 for details)
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...