'12 • PAC-T-174
None
No display
Keeps flashing
Keeps flashing
Stays OFF
2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Remote controller does not display
anything after the power on.
NO
NO
YES
YES
YES
Is DC10V or
higher detected at remote controller connection
terminals?
Is DC10V or higher
detected on remote controller wires if
the remote controller is
removed?
Are wires
connected properly between the
indoor/outdoor units?
NO
Defective remote controller
Defective remote controller
Defective connecting wire.
Defective remote controller
wire (Short-circuit, etc.)
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty indoor control PCB
• Defective remote controller
• Broken remote controller wire
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
373
-
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...