319
-
'12 • PAC-T-174
(4)
Outdoor unit fan control
(a) Outdoor unit fan tap and fan motor speed
Unit: min
-1
Model
Mode
Fan motor tap
100-140
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
350
600
740
820
870
910 (950)
(2)
Heating
200
350
600
740
820
870
910 (950)
(2)
200, 250
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
370
560 (600)
(3)
820
850
910
950
Heating
200
370
560 (600)
(3)
820
850
910
950
Notes (1) Fan motor speed for model 200 and 250 are same for both top and bottom lines
(2) Value in ( ) are for the model 125, 140.
(3) Value in ( ) are for the model 250.
(b) Fan tap control during Cooling/Defumidifying operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
zone
zone
zone
zone
zone
Tap 5
Tap 5
Tap 5
Tap 4
zone
Tap 5
Tap 5
Tap 4
(1)
Tap 3
zone
Tap 4
Tap 4
(1)
Tap 3
Tap 2
zone
Tap 3
Tap 3
Tap 2
Tap 1
zone
zone
Outdoor air temp. (˚C)
15
18
zone
30
37
zone
46
48
zone
Outdoor unit heat exchanger temp. (˚C)
20
30
zone
33
40
zone
43
53
zone
(c) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
zone
zone
zone
zone
Tap 3
Tap 3
Tap 4
zone
Tap 3
Tap 4
(1)
Tap 5
zone
Tap 4
Tap 5
Tap 6
3
9
12
15
-2
0
1
3
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
zone
zone
zone
zone
zone
zone
(d) Outdoor unit fan control at cooling low outdoor air
1)
When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone in the cooling/dehumidifying mode, it has elapsed 20
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
5
10
Retained
Outdoor unit fan speed
-10min
-1
20
30
Outdoor unit fan speed
+10min
-1
zone
zone
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
Note (1) If the “silent mode start” signal is received from the remote controller,
the speed changes from Tap 4 to Tap 3.
Note (1) If the “silent mode start” signal is received from the remote controller, the speed changes
from Tap 4 to Tap 3.
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...