402
-
'12 • PAC-T-174
E51
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
Is DC15V
detected between
②
and
③
on CNI3?
Is DC15V
detected after disconnecting
outdoor fan motor?
YES
YES
NO
• Model FDC100-140VN
• Model FDC100-140VS and FDC200, 250VS
Replace immediately the inverter PCB and the power transistor.
Note(1) Under anomalous conditions,
the voltage becomes less than
DC14V.
Note(2) How to check the voltage between
②
and
③
of CNI3?
⑴ ⑵
⑴
Replace inverter PCB
If not solved, replace
Noise filter PCB as well.
Replace outdoor fan motor.
Replace outdoor control
PCB
If not solved, replace
inverter PCB as well.
2. Error detection method
When power transistor anomaly
is detected for 15 minutes
continuously
3. Condition of Error displayed
Same as above
4. Presumable cause
• Outdoor fan motor anomaly
• Inverter PCB anomaly
• Outdoor control PCB anomaly
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1 time flash
Keeps flashing
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
6 times flash or 2 times flash
Yellow LED or Red LED Green LED
Inverter and fan motor anomaly
③
②
② : 15V (+)
③ : GND (−)
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...