'12 • PAC-T-174
(c) Calculation of total operation characteristics
Since the operation characteristics of V Multi system depend on combination of indoor unit, calculate the total operation characteristics
of the system by using the formulas below according to speciations of each indoor unit or outdoor unit.
1) 1 Phase models
a) Total power consumption
Total power consumption (kW) = Power consumption of outdoor unit +
¤
(Power consumption of indoor unit)
b) Total running current
Total running current (A) = Running current of outdoor unit +
¤
(Running current of indoor unit)
c) Total power factor
Total power factor (%) = [Total power consumption (W) / Total running current (A)
s
Power source]
s
100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 220 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC140VN × 1 unit
Indoor unit: FDT71VF × 2 units
Item
Model
FDC140VN
FDT71VF
Operation characteristics of each unit
(Cooling/Heating)
Power consumption (kW)
Running current (A)
0.08/0.08
0.40/0.40
4.51/4.40
20.4/19.5
①
Total power consumption (kW)
(Cooling) 4.51 + (0.08 × 2) = 4.67
(Heating) 4.40 + (0.08 × 2) = 4.56
②
Total running current (A)
(Cooling) 20.4 + (0.40 × 2) = 21.2
(Heating) 19.5 + (0.40 × 2) = 20.3
③
Total power factor (%)
(Cooling) × 100 = 99 %
(Heating) × 100 = 99 %
4.67 × 1000
21.2 × 220
4.56 × 1000
20.3 × 220
.
.
.
.
2) 3 Phase models
a) Total power consumption
Total power consumption (kW) = Power consumption of outdoor unit +
¤
(Power consumption of indoor unit)
b) Total running current
Total running current (A) = Running current of outdoor unit + [
¤
(Running current of indoor unit) × 1/3]
c) Total power factor
Total power factor (%) = [Total power consumption (W) /
√
× Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
3
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...