435
-
Error code
Remote controller:
Content
1 time flash
Keeps flashing
Keeps flashing
5 times flash
ON
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
E36
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
micro computer control function for corresponding models.
Are the
characteristics of
discharge pipe temperature
thermistor
normal?
Is the
discharge pipe temperature
control normal?
NO
YES
Is the
temperature (measured
actually) at detection of
error correct?
YES
YES
Is the
discharge pipe
temperature error persisted
during cooling
operation?
NO
* For the characteristics of discharge
pipe temperature, refer to E39.
YES
NO
NO
Replace discharge pipe
temperature thermistor.
Insufficient refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
Defective outdoor control
PCB
➞
Replace.
Check unit side:
• Isn’t filter clogged?
• Are adequate indoor,
outdoor unit installation
spaces?
• Isn’t there any short-
circuit of air?
• Isn’t there any fouling,
clogging on indoor heat
exchanger?
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
3.
Condition of Error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor control
PCB
• Defective discharge pipe
temperature thermistor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note:
Discharge pipe
temperature error
-
435
-
'12 • PAC-T-174
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...