21
-
'12 • PAC-T-174
Model
Item
FDT140VSTVF
Indoor unit
FDT50VF (3 units)
Outdoor unit
FDC140VS
Panel
T-PSA-3BW-E
Power source
380-415V 3N~50Hz / 380V 3N~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
14.0 [5.0 (Min.)~14.5 (Max.)]
16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption
kW
4.65
4.63
Running current
A
6.9 / 7.4
6.8 / 7.1
Power factor
%
97 / 95
98 / 99
Inrush current
A
5 < Max.running current 15 >
Sound Pressure Level
dB(A)
P-Hi : 39 Hi : 33 Me : 31 Lo : 30
51
Exterior dimensions
Height × Width × Depth
mm
Unit 246 × 840 × 840
Panel 35 × 950 × 950
845 × 970 × 370
Exterior appearance
(Munsell color)
Plaster White
(
6.8Y8.9/0.2) near equivalent
Stucco White
(
4.2Y7.5/1.1) near equivalent
Net weight
kg
UNIT 22 PANEL 5.5
83
Refrigerant equipment
Compressor type & Q'ty
—
RMT5126MDE3 × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.9 M-MA68
Heat exchanger
Louver fin & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Turbo fan × 1
Propeller fan × 1
Motor <Starting method>
W
50 < Direct line start >
86 < Direct line start >
Air flow (Standard)
CMM
P-Hi : 20
Hi : 18 Me : 16 Lo : 14
Cooling : 75 , Heating : 73
External static pressure
Pa
0
0
Outside air intake
Possible
—
Air filter, Q'ty
Pocket plastic net × 1 (Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor)
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
wired : RC-EX1A , RC-E5 (option) wireless : RCN-T-36W-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
mm
Liquid line : I/U
φ
6.35 (1/4")
②φ
9.52 (3/8") × 0.8
①φ
9.52 (3/8") × 0.8 O/U
φ
9.52 (3/8")
Gas line : I/U
φ
12.7 (1/2")
②φ
12.7 (1/2") × 0.8
①φ
15.88 (5/8") × 1.0 O/U
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Max.50m
Vertical height difference between
outdoor unit and indoor unit
Max.30m (Outdoor unit is higher) See page 155
Max.15m (Outdoor unit is lower)
Refrigerant Quantity
R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump
Built-in Drain pump
—
Drain
Hose Connectable with VP25
Holes size
φ
20 × 3pcs
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
IPX4
Standard Accessories
Mounting kit, Drain hose
Edging
PJF000Z294
Adapted to
RoHS directive
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option).
① :
Pipe of O/U~Branch,
② :
Pipe of Branch~I/U
(7) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
7˚C
6˚C
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...