203
-
'12 • PAC-T-174
Piping length limitations
Model
Item
200, 250
Max. one way piping length
70m
100, 125, 140
50m
Max. vertical height difference
Outdoor unit is higher 30m
Outdoor unit is lower 15m
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling and heating capacity
Net cooling capacity =
10.0
×
1.00
×
0.978
×
.
=.
9.7kW
Example : The net cooling capacity of the model FDUM100VNVF with the air flow “P-High”, the piping length of 15m, the outdoor
unit located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0
℃
and outdoor dry-bulb temperature 35
℃
is
Net cooling total capacity
of FDUM100VNVF
(Outdoor temp. : 35
℃
DB
Indoor temp. : 19
℃
WB)
shown in table 1.9.1
Air flow : P-Hi
shown in table 1.9.2
Piping length :15m
(Gas pipe size is
φ
15.88)
shown in table 1.9.3
Height diff. :5m
(Outdoor unit : below)
shown in table 1.9.4
0.99
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...