'12 • PAC-T-174
(
ⅰ
)
Cautions
1) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning.
When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work.
2) When taking out printed circuit boards, be sure to do so without exerting force on the circuit boards or package
components.
3) When disconnecting and connecting connectors, take hold of the connector housing and do not pull on the lead wires.
(
ⅱ
)
Items to check before troubleshooting
1) Is the air conditioner running? Is it displaying any self-diagnosis information?
2) Is a power supply with the correct voltage connected?
3) Are the control lines connecting the indoor and outdoor units wired correctly and connected securely?
4) Is the outdoor unit,s service valve open?
(
ⅲ
)
Troubleshooting procedure (If the air conditioner does not run at all)
If the air conditioner does not run at all, diagnose the trouble using the following troubleshooting procedure.
Important
When all the following conditions are met, we say that the air conditioner will not run at all.
1) The RUN light does not light up.
2) The flaps do not open.
3) The indoor unit fan motors do not run.
4) The self-diagnosis display does not function.
(a) Cautions
1) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning.
YES
YES
NO
NO
NO
YES
Troubleshooting procedure (If the air conditioner does not run at all)
Is the correct voltage
connected for the power
supply?
With the power off, do
the ßaps open manually,
then close again when
the power is turned on?
Replace the indoor printed
circuit board and perform an
operation check.
Make sure the correct volt-
age is connected, then per-
form an operation check.
Is the current fuse on the in-
door unit,s board broken?
Proceed to the indoor printed
circuit board check.
If the package components
are not damaged, replace
the fuse and perform an op-
eration check again.
* If the voltage is correct, it will be
within the following voltage range.
198 ~ 264 V
When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work.
2) When taking out printed circuit boards, be sure to do so without exerting force on the circuit boards or package components.
3) When disconnecting and connecting connectors, take hold of the connector housing and do not pull on the lead wires.
(b) Items to check before troubleshooting
1) Is the air conditioner running? Is it displaying any self-diagnosis information?
2) Is a power supply with the correct voltage connected?
3) Are the control lines connecting the indoor and outdoor units wired correctly and connected securely?
4) Is the outdoor unitÕs service valve open?
(c) Troubleshooting procedure (If the air conditioner does not run at all)
If the air conditioner does not run at all, diagnose the trouble using the following troubleshooting procedure.
Important
When all the following conditions are met, we say that the air conditioner will not run at all.
1) The RUN light does not light up.
2) The flaps do not open.
3) The indoor unit fan motors do not run.
4) The self-diagnosis display does not function.
(b)
SRK series
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...