64
-
'12 • PAC-T-174
Model
Item
FDUM140VNVF
Indoor unit
FDUM140VF
Outdoor unit
FDC140VN
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
14.0 [ 5.0 (Min.)~14.5 (Max.)]
16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption
kW
4.95
4.69
Running current
A
22.2 / 23.2
21.0 / 22.0
Power factor
%
97
97
Inrush current
A
5 < Max.running current 24 >
Sound Pressure Level
dB(A)
P-Hi : 47 Hi : 40 Me : 35 Lo : 30
51
Exterior dimensions
Height x Width x Depth
mm
280 × 1,370 × 740
845 × 970 × 370
Exterior appearance
(Munsell color)
—
Stucco White
(
4.2Y7.5/1.1) near equivalent
Net weight
kg
54
81
Refrigerant equipment
Compressor type & Q'ty
—
RMT5126MDE2 × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.9 M-MA68
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 3
Propeller fan × 1
Motor <Starting method>
W
100 + 200 < Direct line start >
86 < Direct line start >
Air flow (Standard)
CMM
P-Hi : 48 Hi : 35 Me : 28 Lo : 22
Cooling : 75 , Heating : 73
External static pressure
Pa
Standard : 60 Max : 100
0
Outdoor air intake
Possible
—
Air filter, Q'ty
Procure locally
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor)
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
wired : RC-E5 (option) wireless : RCN-KIT3-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
mm
Liquid line : I/U
φ
9.52 (3/8") Pipe
φ
9.52 (3/8") × 0.8 O/U
φ
9.52 (3/8")
Gas line : I/U
φ
15.88 (5/8")
φ
15.88 (5/8") × 1.0
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Max.50m
Vertical height difference between
outdoor unit and indoor unit
Max.30m (Outdoor unit is higher) 1.See page 154
Max.15m (Outdoor unit is lower)
Refrigerant Quantity
R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump
Built-in Drain pump
—
Drain
Hose Connectable with VP20
Holes size
φ
20 × 3pcs
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
IPX4
Standard Accessories
Drain hose
Edging
Adapted to
RoHS directive
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
External static pressure of indoor unit
Operation
DB
WB
DB
WB
Pa
Cooling
27˚C
19˚C
35˚C
24˚C
60
Heating
20˚C
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Static pressure of optional air filter "UM-FL3EF" is 5Pa initially.
(6) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
PJG000Z032
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...