404
-
'12 • PAC-T-174
E54
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Replace the low pressure sensor.
Are the
connection of low pressure
sensor connectors (at sensor side
and PCB side) OK?
Are the
pressure (actual
measurement) matched with the value
indicated on the remote
controller?
Is
normal condition
restored?
NO
YES
Correct low pressure sensor
connector connection.
Is refrigerant amount
charged properly?
Is there any anomaly on the
refrigeration circuit?
Defective outdoor control
PCB
➞
Replace.
(Defective low pressure
sensor input circuit)
OK
2. Error detection method
When anomalous voltage
(pressure) is detected
3. Condition of Error displayed
If the pressure sensor detects 0V
or lower and 3.49V or higher for
5 seconds continuously within
2 minutes to 2 minutes 20
seconds after compressor ON,
the compressor stops. When
the compressor is restarted
automatically after 3-minuts
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
• Defective low pressure sensor
connection
• Defective low pressure sensor
• Defective outdoor control
PCB
• Improper amount of
refrigerant
• Anomalous refrigeration
circuit
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1 time flash
Keeps flashing
Yellow LED or Red LED Green LED
Indoor control PCB
Stays OFF
Keeps flashing
Keeps flashing
Content
Keeps flashing
Low pressure sensor anomaly
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...