335
-
'12 • PAC-T-174
Replace and set up the PCB according to this instruction.
①
Set to an appropriate address and function using switch on PCB.
Select the same setting with the removed PCB.
②
Set to an appropriate capacity using the model selector switch(SW6).
Select the same capacity with the PCB removed from the unit.
③
Replace the PCB
1. Fix the PCB so as not to pitch the cords.
2. Connect connectors to the PCB. Connect a cable connector with the PCB connector of the same color.
3.Do not pass CPU surrounding about wirings.
④
Control PCB
Parts mounting are different by the kind of PCB.
〇:ON -:OFF
Part number
SW2 (Blue)
Address setting
SW5
Master/Slave
setting
SW7
Function setting
CNT(Blue)
External switch
CNJ(White)
Louver motor
CNN(Yellow)
Thermistor
(Heat exchanger)
CNI(Blue)
Float SW
CNH(Black)
Thermistor
(Return air)
CNW3(Red)
Power PCB
CNB(White)
Remote
controller
CNV2(Black)
Auto lift
CNG(Blue)
CNZ(White)
HA
CNE(White)
RAM checker
CNC(Red)
Humidity
sensor
CNW4(Blue)
Power PCB
SW6
Capacity setting
CNV(Red)
Auto lift
item
switch
Address
SW2
-
〇
Content of control
Plural indoor units control by 1 remote controller
Test run
SW7-1
Normal
Operation check/drain motor test run
SW6
ON
1 2 3 4
Example setting for 50VF
SW6
-1
-2
-3
-4
-
〇
50VF
〇
-
〇
〇
60VF
〇
-
•
Control PCB
◆
Model FDTC series
PSB012D931F
C
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...