1.11.4 Operation control function by the outdoor controller
(1)
Determination of compressor speed (frequency)
Required frequency
(a) Cooling/dehumidifying operation
Unit: rps
Model
100
125
140
200
250
Max. required
frequency
Usual operation
90
105
105
100
120
Silent mode, outdoor temperature
≦
15°C
60
80
85
70
80
Min. required frequency
20
20
20
30
30
(b) Heating operation
Unit: rps
Model
100
125
140
200
250
Max. required
frequency
Usual operation
90
105
110
100
120
Silent mode
60
80
85
70
80
Min. required frequency
20
20
20
30
30
(c) If the indoor unit fan speed becomes “Me” or “Lo”, Max required frequentcy goes down accordingly depending on indoor
unit model.
(d) Max. required frequency under high outdoor air temperature in cooling mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Unit: rps
Model
100
125
140
200
250
Max. required
frequency
Outdoor air temperature is
40°C or higher
75
90
96
75
98
Outdoor air temperature is
46°C or higher
75
75
75
66
66
(e) Max. required frequency under outdoor air temperature in heating mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Unit: rps
Model
100
125
140
200
250
Max. required
frequency
Outdoor air temperature is
18°C or higher
60
80
85
70
80
(f) Selection of max. required frequency by heat exchanger temperature
1)
Maximum required frequency is selected according to the outdoor unit heat exchanger temperature (Tho-R) during
cooling/dehumidifying or according to the indoor unit heat exchanger temperature (Th
I
-R) during heating mode.
2)
When there are 3 indoor unit heat exchanger temperatures (Th
I
-R), whichever the highest applies,
Unit: rps
Model
100
125
140
200
250
Max. required
frequency
Cooling/
dehumidifying
Outdoor unit heat exchanger
temperature is 56°C or higher
90
100
100
100
120
Heating
Indoor unit heat exchanger
temperature is 56°C or higher
90
100
100
100
120
Note (1) Value in ( ) are for the 3 phase models.
(g) When any of the controls from (a) to (f) above may duplicate, whichever the smallest value among duplicated controls is
taken as the maximum required frequency.
(h) During heating, it is operated with the maximum required frequency until the indoor unit heat exchanger temperature
becomes 40°C or higher.
(2)
Compressor start control
(a) Compressor starts upon receipt of the thermostat ON signal from the indoor unit.
(b) However, at initial start after turning the power supply breaker, it may enter the standby state for maximum 30 minutes
(“ PREPARATION” is displayed on the remote controller) in order to prevent the oil loss in the compressor.
If the cooling/dehumidifying/heating operation is selected from the remote controller when the outdoor unit is in the
standby state, “ PREPARATION” is displayed for 3 seconds on the remote controller.
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...