'12 • PAC-T-174
(d) Anomaly detection control by the high pressure switch (63H1)
1)
If the pressure rises and operates the high pressure switch (opens at 4.15MPA/closes at 3.15MPa), the compressor stops.
2)
Under any of the following conditions, E40 is displayed and it enters the anomalous stop mode.
a) When it occurs 5 times within 60 minutes that pressure rises and the compressor is stopped by 63H1.
b) When 63H1 has been in the open state for 60 minutes continuously, including the stop of compressor.
(e) Low pressure control
1)
Protective control
If the value detected by the low pressure sensor (LPT) exceeds the setting value, the compressor speed (frequency)
is controlled to restrain the drop of pressure.
Retention
Reduces compressor frequency
at every 30 seconds.
Reset
0.150
0.189
Low pressure (MPa)
2)
Anomalous stop control
a) When a value detected by the low pressure sensor (LPT) satisfies any of the following conditions, the
compressor stops to run for its protection.
i) When the low pressure drops to 0.079MPa or under for 15 seconds continuously.
ii) At 10 minutes after the start of compressor, the suction overheat becomes 30°C and the low pressure
becomes 0.15MPa or under for 60 seconds continuously.
b) E49 is displayed under any of the following conditions and it enters the anomalous stop mode.
i) When the low pressure drops 3 times within 60 minutes and the compressor stops under any of the above conditions.
ii) When a value detected with the low pressure sensor becomes 0.079MPa or under for 5 minutes, including
the stop of compressor.
c) However, when the control condition
➀
is established during the compressor protection start III, E49 is
displayed at initial stop and it enters the anomalous stop mode.
(f)
Compressor pressure ratio protection control
1)
During heating operation, if the indoor unit heat exchanger temperature (Th
I
-R) and the low pressure sensor (LPT)
exceed the setting values at 10 minutes after the start of compressor, the compressor speed (frequency) is controlled
to protect the compressor.
2)
This control is not performed during the outdoor fan ON and for 10 minutes from the start of outdoor unit fan.
3)
This control is not performed during defrosting operation and at 10 minutes after the reset of defrosting operation.
4)
When there are 3 indoor unit heat exchanger temperatures (Th
I
-R), the highest temperature is detected.
65
°C
33
°C
0.150
0.425
Low pressure (MPa)
Indoor unit heat e
xchanger temp. (°C)
Resert
Reduces compressor frequency at each minute.
(g) Over-current protection current safe controls I, II
Detecting the outdoor unit inverter input (primary) current and the output (secondary) current, if the current values exceed
setting values, the compressor speed (frequency) is controlled to protect the inverter.
Retention
Reduces frequency
at each minute.
Reset
B
A
Current (A)
12
14
16
18
20
22
24
50
40
60
70
80
90
100 110 120 130
Control or reset v
alv
e (A)
Compressor speed (frequency) (rps)
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed.
Reset valve B
Control valve A
Model
Cooling
Heating
Control
value A
Reset
value B
Control
value A
Reset
value B
Primary
current
side
100
13.5 (23.0) 12.5 (22.0) 13.5 (23.0) 12.5 (22.0)
125,
140
13.5 (23.0) 12.5 (22.0) 13.5 (23.0) 12.5 (22.0)
200
17.0
16.0
17.0
16.0
250
20.0
19.0
20.0
19.0
Secandary
current
side
100 13.0 (Fig.C) 12.0 (Fig.C) 13.0 (Fig.C) 12.0 (Fig.C)
125,
140 13.0 (Fig.C) 12.0 (Fig.C) 13.0 (Fig.C) 12.0 (Fig.C)
200
Not implemented
250
Note (1) Value in ( ) are for the single phase models.
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...