249
-
'12 • PAC-T-174
Control plural indoor units by a single remote controller.
Master/ slave setting when more than one remote control unit are used
Electrical Wiring Connection
②
Remote Control, Wiring and functions
③
Operation and confirmation from remote controller
Indoor Unit (1)
Address “0”
Indoor Unit (2)
Address“1”
Indoor Unit (16)
Address“F”
Remote controller
Remote controller line (no polarity)
Remote
controller
“Master”
Remote
controller
“Slave”
Indoor Unit
Remote controller line
(no polarity)
Installation and wiring of remote controller
ELECTRIC WIRING WORK INSTRUCTION
Security instructions
Control mode switching
CAUTION
WARNING
●
●
●
●
●
●
●
Do not mingle solid cord and stranded cord on power source and signal side
terminal block.
In addition, do not mingle difference capacity solid or stranded cord.
Inappropriate cord setting could cause loosing screw on terminal block, bad electrical
contact, smoke and fire.
●
●
●
●
●
●
●
●
●
●
PSBO12D999
④
Avoid using multi-core cables to prevent malfunction.
⑤
Keep remote controller line away from earth (frame or any metal of building).
⑥
Make sure to connect remote controller line to the remote controller and terminal block of indoor
unit. (No polarity)
①
A remote controller can control plural indoor units (Up to 16).
In above setting, all plural indoor units will operate under same mode and temperature setting.
②
Connect all indoor units with 2 core remote controller line.
③
Set unique remote control communication address from "0" to "F" to each inside unit by the
rotary switch SW2 on the indoor unit's PCB.
A maximum of two remote control units can be connected to one indoor unit (or one group of
indoor units.)
The air conditioner operation follows the last operation of the remote controller regardless of the
master/slave setting of it.
Acceptable combination is "two (2) wired remote controllers", "one (1) wired remote controller
and one (1) wireless kit" or "two (2) wireless kits".
Set one to "Master" and the other to "Slave".
Note:The setting "Remote control unit sensor enabled" is only selectable with the master remote
control unit in the position where you want to check room temperature.
●
●
●
●
Cable connection for a V multi configuration installation
Method of setting Master/Slave of indoor unit
(Factory setting: “Master”)
PCB
SW
SW5-1
OFF
OFF
OFF
ON
ON
ON
ON
OFF
SW5-2
Indoor Unit
Master
Slave 1
Slave 2
Slave 3
AIR CON NO.
①
Connect the same pairs number of terminal block "
①
,
②
,
and
③
"and " X and Y " between
master and slave indoor units.
②
Do the same address setting of all inside units belong to same refrigerant system by rotary
switch SW2 on indoor unit's PCB (Printed circuit board).
③
Set slave indoor unit as "slave 1" through "slave 3" by address switch SW5-1, 5-2 on PCB.
④
When the button on the remote control unit is pressed after turning on the power, an
indoor unit's address number will be displayed. Do not fail to confirm that the connected indoor
unit's numbers are displayed on the remote control unit by pressing the or button.
●
DO NOT install it on the following places
①
Places exposed to direct sunlight
②
Places near heat devices
③
High humidity places
④
Hot surface or cold surface enough to generate condensation
⑤
Places exposed to oil mist or steam directly.
⑥
Uneven surface
Electrical wiring work must be performed by an electrician qualified by a local power provider according to
the electrical installation technical standards and interior wiring regulations applicable to the installation site.
Be sure to have the electrical wiring work done by qualified electrical installer,
and use exclusive circuit.
Power source with insufficient capacity and improper work can cause electric shock and fire.
Use specified wire for electrical wiring, fasten the wiring to the terminal securely,
and hold the cable securely in order not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
Arrange the electrical wires in the control box properly to prevent them from
rising. Fit the lid of the services panel property.
Improper fitting may cause abnormal heat and fire.
Use the genuine optional parts. And installation should be performed by a
specialist.
If you install the unit by yourself, it could cause water leakage, electric shock and fire.
Turn off the power source during servicing or inspection work.
If the power is supplied during servicing or inspection work, it could cause electric
shock and injury by the operating fan.
Perform earth wiring surely.
Do not connect the earth wiring to the gas pipe, water pipe, lightning rod and telephone earth
wiring. Improper earth could cause unit failure and electric shock due to a short circuit.
Make sure to install earth leakage breaker on power source line.
(countermeasure thing to high harmonics.)
Absence of breaker could cause electric shock.
Do not use any materials other than a fuse of correct capacity where a fuse
should be used.
Connecting the circuit by wire or copper wire could cause unit failure and fire.
Do not turn off the power source immediately after stopping the operation.
Be sure to wait for more than 5 minutes. Otherwise it could cause water leakage or
breakdown.
Do not control the operation with the circuit breaker.
It could cause fire or water leakage. In addition, the fan may start operation
unexpectedly and it may cause injury.
Do not repair by yourself. And consult with the dealer about repair.
Improper repair may cause water leakage, electric shock or fire.
Consult the dealer or a specialist about removal of the air conditioner.
Improper installation may cause water leakage, electric shock or fire.
Shut off the power before electrical wiring work.
It could cause electric shock, unit failure and improper running.
Use the circuit breaker of correct capacity. Circuit breaker should be the one
that disconnect all poles under over current.
Using the incorrect one could cause the system failure and fire.
Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause electric shocks.
Use power source line of correct capacity.
Using incorrect capacity one could cause electric leak, abnormal heat generation and fire.
Read the “SAFETY PRECAUTIONS” carefully first of all and then strictly follow it during the
installation work in order to protect yourself.
The precautionary items mentioned below are distinguished into two levels,
and .
: Wrong installation would cause serious consequences such as injuries or death.
: Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow
them by any means.
The meanings of “Marks” used here are as shown on the right:
Accord with following items. Otherwise, there will be the risks of electric shock and
fire caused by overheating or short circuit.
①
Install remote controller referring to the attached installation manual.
②
Wiring of remote controller should use 0.3mm
2
×
2 core wires or cables.
The insulation thickness is 1mm or more. (on-site configuration)
③
Maximum prolongation of remote control wiring is 600 m.
If the prolongation is over 100m, change to the size below.
But, wiring in the remote controller case should be under 0.5mm
2
. Change the wire size
outside of the case according to wire connecting. Waterproof treatment is necessary at the
wire connecting section. Be careful about contact failure.
100 - 200m ........................ 0.5mm
2
× 2 cores
Under 300m ....................... 0.75mm
2
× 2 cores
Under 400m ....................... 1.25mm
2
× 2 cores
Under 600m ....................... 2.0mm
2
× 2 cores
●
Switch No.
SW2
SW5-1
SW5-2
SW6-1
~
4
SW7
-
1
Control Content
Indoor unit address (0-Fh)
Master/Slave Switching (plural /Slave unit Setting)
Model capacity setting
ON
Operation check, Drain motor test run
OFF
Normal operation
The control content of indoor units can be switched in following way. ( is the default setting)
Cable connection for single unit installation
①
As for connecting method of power source, select from following connecting patterns. In principle, do
not directly connect power souce line to inside unit.
As for exceptional connecting method of power souce, discuss with the power provider of the
country with referring to technical documents, and follow its instruction.
②
For cable size and circuit breaker selection, refer to the outdoor unit installation manual.
Never do it under any circumstances.
CAUTION
CAUTION
Always do it according to the instruction.
●
Electrical wiring work must be performed by an electlician an qualified by a local power
provider. These wiring specifications are determined on the assumption that the following
instructions are observed:
①
Do not use cords other than copper ones.
Do not use any supply line lighter than one specified in parentheses for each type below.
-braided cord (code designation 60245 IEC 51), if allowed in the relevant part 2;
-ordinary tough rubber sheathed cord (code designation 60245 IEC 53);
-flat twin tinsel cord (code designation 60227 IEC 41);
-ordinary polyvinyl chloride sheathed cord (code designation 60227 IEC 53);
②
Connect the power supply to the outdoor unit.
③
Pay extra attention so as not to confuse signal line and power source line connection, because an error in their connection can be
burn all the boards at once.
●
Screw the line to terminal block without any looseness, certainly.
●
Do not turn on the switch of power source, before all of line work is done.
●
Provide a dedicated branching circuit and never share a branching circuit with other
equipment. If shared, disconnection at the circuit breaker may occur, which can cause
secondary damage.
●
Use three-core cable as wiring between indoor and outdoor unit. As for detail, refer to
"INSTALLATION MANUAL" of outdoor Unit.
●
Set earth of D-type.
●
Do not add cord in the middle of line (of indoor power source, remote controller and signal)
route on outside of unit. If connecting point is flooded, it could cause problem as for electric or
communication.
(In the case that it is necessary to set connecting point on the signal line way, perform
thorough waterproof measurement.)
●
Run the lines (power source, remote controller and "between indoor and outdoor unit") upper
ceiling through iron pipe or other tube protection to avoid the damage by mouse and so on.
●
Keep "remote controller line" and "power source line" away from each other on constructing
of unit outside.
●
Do not connect the power source line [220V/240V/380V/415V] to signal side terminal block.
Otherwise, it could cause failure.
●
Connection of the line ("Between indoor and outdoor unit", Earth and Remote controller)
①
Remove lid of control box before connect the above lines, and connect the lines to terminal block according to number pointed on
label of terminal block.
In addition, pay enough attention to confirm the number to lines, because there is electrical polarity except earth line.
Furthermore, connect earth line to earth position of terminal block of power source.
②
Install earth leakage breaker on power source line. In addition, select the type of breaker for inverter circuit as earth leakage breaker.
③
If the function of selected earth leakage breaker is only for earth-fault protection, hand switch (switch itself and type "B" fuse) or
circuit breaker is required in series with the earth leakage breaker.
④
Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations.
The isolator should be set in the box with key to prevent touching by another person when servicing.
④
Function of CNT connector of indoor printed circuit board
1
2
1
2
3
4
5
6
1
2
1
2
3
4
5
6
Red
C
N
T
(
Blue 6P
)
+12
C
N
TA
(
Blue 2P
)
+12
Indoor units control box
Black
X
R1
X
R1
X
R2
X
R3
X
R4
X
R2
X
R3
X
R5
X
R6
X
R4
X
R5
Yellow
Blue
Brown
Orange
White
Black
Yellow
Blue
Brown
Orange
Orange
Common
Output 1
Output 2
Output 3
Output 4
Remote start/stop
button or timer point
AC100V
DC12V
DC24V
Input
power 1
Input
power 2
X
R6
AC100V
DC12V
DC24V
Note
(
1
)
0.3mm
2
×2m
Note
(
1
)
0.3mm
2
×2m
Note (1): Do not use the length over 2 meter
Printed circuit board
Remote start/stop kit
0.75mm
2
×0.2m
Butt splice
(
Application coverage
0.75
〜
1.25mm
2
)
●
CNT connector (local) vendor model
Connector : Made by molex 5264-06
Terminals : Made by molex 5263 T
●
CNTA connector is installed on FDT, etc. Refer to the spec. drawings.
CNTA connector (local) vendor model
Connector : Made by JST XAP02V-1-E
Terminals : Made by JST SXA-01T-P0.6
●
Function
* Refer to I/U settings.
Output 1
Air conditioner operation output (When the air conditioner ON: X
R1
= ON)
Output 2
Heating output
Output 3
Thermostat ON output (When the thermostat ON: X
R3
= ON)
Output 4
Air conditioner check ON (When checking air conditioner: X
R4
= ON)
X
R5
OFF
⇒
ON: Air conditioner operates.
At shipping
X
R5
ON
⇒
OFF: Air conditioner stops.
*Functions and controls may vary depending on the switching at site.
Input
X
R6
OFF
⇒
ON: Air conditioner operates.
At shipping
X
R6
ON
⇒
OFF: Air conditioner stops.
*Functions and controls may vary depending on the switching at site.
Input 2
(FDT etc.)
Press the CHECK button.
⇒
“ ” is displayed.
⇒
Press the (SET) button.
⇒
“ ” is displayed.
⇒
Press the “ ” button.
⇒
Select one of addresses
for connected indoor units by pressing the
▲
or
▼
button.
⇒
Press the (SET) button.
⇒
“ ” is displayed.
⇒
Select data by pressing the
▲
or
▼
button.
Press the CHECK button.
⇒
button.
⇒
ERR DATA
.
⇒
Press the (SET) button.
⇒
“ ” is displayed.
⇒
Data.
Operation from RC-EX1A
1 Check the number of units connected in the remote control system.
It checks sub units of twin, triple or W-twin connection.
“Menu”
⇒
“Next”
⇒
“Service & Maintenance”
⇒
“Input password”
⇒
“IU address”
2 Check if each unit is connected properly in the remote control system.
It cannot check main and sub units of twin, triple or W-twin connection.
When the operation is stopped
,
“Menu”
⇒
“Next”
⇒
“Service & Maintenance”
⇒
“Input password”
⇒
”IU address”
⇒
”check run mode”
3 Setting main/slave remote controllers
“Menu”
⇒
“Next”
⇒
“R/C function settings”
⇒
“Input password”
⇒
“Main/Sub of R/C”
4 Checking operation data
“Menu”
⇒
“Next”
⇒
“Service & Maintenance”
⇒
“Input password”
⇒
“Operation data”
5 Checking inspection display
“Menu”
⇒
”Next”
⇒
”Service & Maintenance”
⇒
“Input password”
⇒
”Inspection display”
6 Cooling test run from remote controller
“Menu”
⇒
“Next”
⇒
“Installation settings”
⇒
“Input password”
⇒
“Test run”
⇒
“Cooling test run”
⇒
“Start”
7 Trial operation of drain pump from remote controller
“Menu”
⇒
“Next”
⇒
“Installation settings”
⇒
“Input password”
⇒
“Test run”
⇒
“Drain pump test run“
⇒
”Run”
Operation from RC-E4, RC-E5
Press button to display the IU
address. Press the or button and check
addresses of connected indoor units one by one.
If AIR CON NO. button is pressed when the operation is stopped,
the indoor unit address is displayed. If you select one of
addresses for connected indoor units by pressing the
or
button and press the (MODE) button, the unit starts to blow air.
Set SW1 to “Slave” for the slave remote control
unit.
AIR CON NO
①
Start the system by pressing the button.
②
Select “ (Cool)” with the (MODE) button.
③
Press the
TEST
button for 3 seconds or longer.
The screen display will switch to: “ ”
④
When the (SET) button is pressed while “ ”
is indicated, a cooling test run will start.
The screen display will switch to “ ”.
①
Press the TEST button for three seconds or longer.
The display will change “ ”
②
Press the button once and cause “ ” to be
displayed.
③
When the (SET) button is pressed, a drain pump operation
will start. Display: “ ”
Three-phase model
Single-phase model
L N
Remote controller
Remote controller
Power source
Doner source
Indoor Unit
Outdoor Unit
Indoor Unit
Outdoor Unit
Earth
Circuit breaker
r
k
Circuit breaker
Earth leakage breaker
Power source line
Indoor-Outdoor Connecting line
Remote controller line
Power source line
Indoor-Outdoor Connecting line
Remote controller line
Earth leakage breaker
Earth leakage breaker
Earth
Remote controller
ker
Master
Slave 1
Slave 2
Slave 3
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Outdoor Unit
Earth
Earth
Earth
Earth
Power source
Earth leakage breaker
Twin type
Remote controller line (no polarity)
Double twin type
Triple type
Circuit brea
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...