466
-
'12 • PAC-T-174
Model
Item
FDC100VS
Power source
380-415V 3N~50Hz / 380V 3N~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
10.0 [ 4.0 (Min.)~11.2 (Max.)]
11.2 [ 4.0 (Min.)~12.5 (Max.)]
Sound Pressure Level
dB(A)
49
Exterior dimensions
Height x Width x Depth
mm
845 × 970 × 370
Exterior appearance
(Munsell color)
Stucco White
(4.2Y7.5/1.1) near equivalent
Net weight
kg
83
Refrigerant equipment
Compressor type & Q'ty
RMT5126MDE3 × 1
Starting method
Direct line start
Refrigerant oil
0.9 M-MA68
Heat exchanger
Straight fin & inner grooved tubing
Refrigerant control
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Propeller fan × 1
Motor <Starting method>
W
86 < Direct line start >
Air flow (Standard)
CMM
Cooling : 75, Heating : 73
External static pressure
Pa
0
Shock & vibration absorber
Rubber sleeve (for Compressor )
Electric heater
W
20 (Crank case heater)
Safety equipment
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
mm
Liquid line :
φ
9.52 (3/8")
Gas line :
φ
15.88 (5/8")
Connecting method
Flare piping
Refrigerant line (one way) length
Max.50m
Vertical height difference between
outdoor unit and indoor unit
Max.30m (Outdoor unit is higher) See page 154
Max.15m (Outdoor unit is lower)
Refrigerant Quantity
R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain
Holes size
φ
20 x 3pcs
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IP24
Standard Accessories
Edging
Adapted to
RoHS directive
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z294
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...